Introduction
This manual presents load tables for a number of practical design situations. Tables should be read in conjunction with the systems information as given earlier.
Steadmans have used a flexible approach to the number of rows of sag members, to allow maximum freedom of choice for the designer and Architect. Information on this topic should be obtained from the relevant section of the manual prior to selection of purlins and rails.
Note that if zero rows of sag bars are used then temporary bracing may be required during erection to avoid distortion of purlins and rails.
Load tables are based on calculations to BS 5950-5:1998 using a combination of rational analysis and component testing on sleeve connections. The tables are based on the use of restraining metal cladding. For the cases of non-restraining cladding and hook-bolt fixed cladding the design disk should be used in conjunction with the sag systems.
Purlin Load Tables
Load tables provide unfactored gravity load capacities which are based on the lesser of the purlin working load capacity or as controlled by a deflection limit of Span/180. The tables also provide ultimate load capacities for gravity load, wind uplift and for deflection limits of Span/180 and Span/150. Wind uplift capacity values are given for three conditions, i.e. 0 rows, 1 row and 2 rows of purlin braces, within the limits of the information provided. (Refer to page 4 in the Zed Purlin Systems PDF)
When evaluating factored and unfactored loadings the self weight of the purlin section need not be considered as this effect is included in the load tables, with the exception that the deflection-controlled values are based on deflections only, excluding self weight effects, so that other limits may be adopted by pro-rata.
Purlins are frequently selected on the basis of a gravity load deflection limit of Span/180 but there may be a number of cases, including agricultural buildings, where other limits may apply. In the case of agricultural buildings the designer may choose to select purlins on the basis of the load given for the Span/150 limit, for unfactored loads, and on the basis of the ultimate capacity for factored loadings. Some claddings may require more stringent deflection limits and these may be determined by pro-rata. It is not usual to limit deflections for wind uplift cases but if required the designer can evaluate the unfactored net wind uplift and limit to the deflection-limit capacity given in the tables.
Note that purlin design may be more readily carried out using the Steadmans design software.
Wind loadings should be evaluated to the relevant code of practice and should be increased by a suitable load factor (usually 1.4), with the cladding dead load deducted to give the factored net loading. The load tables apply to roof slopes up to 25 degrees, for steeper slopes the design software should be used or consult Steadmans direct. |